DBI
Detector Base Isolator
Model: DBI
When a communication fault such as a short circuit occurs on the analog detector line connected to the system loop of an R-type fire alarm control panel or repeater panel, this product isolates the affected section of the circuit. By separating the faulted section, it helps maintain stable operation of the rest of the fire alarm system.
Features
· Short-circuit monitoring and automatic recovery · Up to 15 units can be installed per system loop
Specifications
  • ModelDBI
  • Operating VoltageDC24V ± 20%
  • Current Consumption1.5mA
  • Dimensions126(Ø) x 23 mm
  • Weight102g
  • ColorWhite
  • MaterialPC Flame Retardant V2
  • Operating Environment-10 ~ 50℃, 0% ~ 93% RH
  • Communication MethodP-NET (Power Line Communication)
  • Connection CapacityUp to 15 Isolator Bases per system