M2GIO-44
4-CIRCUIT I/O MODULE
Model: M2GIO-44
This product converts activation signals from conventional detectors, manual call points, or electrical contacts into digital input signals and transmits them to a GR-type control panel or repeater panel via the QP-NET communication line. It also processes digital control signals received from the control panel to operate control equipment or alarm devices such as bells and sirens.
Features
· LED flashing indicator for communication status with the control panel / repeater panel · Transmits short-circuit information to the control panel when the repeater output is shorted (built-in POLY SW) · LED indicators for input / output signal status · DIP switch for address setting · Control power input terminal for output control (24VDC power supply connection) · Easy terminal identification
Specifications
  • ModelM2GIO-44
  • Type Approval No.중24-18
  • TypeDC24V, for GR-type system, 4 input circuits, 4 output circuits, Indoor Type
  • KC Registration No.R-R-GSF-M2GIO-44a
  • Input Power / Output CurrentDC24V ± 20% / Max. 0.5A
  • Communication TerminalsP-NET S (Signal), SC (Signal Common)
  • Communication MethodP-NET (PLC Power Line Communication), Polling Address Method
  • IndicatorLED indication during operation (10 LEDs)
  • End-of-Line Resistor10kΩ 1/4W
  • Detector Connection CapacityConventional rate-of-rise and fixed-temperature detectors: Up to 60 per circuit / Conventional photoelectric detectors: Up to 40 per circuit
  • Dimensions89(W) x 85(H) x 23(D) mm
  • Weight110g
  • ColorWhite Case, Brown Sticker
  • MaterialPC
  • Operating Environment-10℃ ~ +50℃, 0% ~ 90% RH